Isodec CE
The Isodec CE consists of an aluminium laminate inner duct, thermally insulated with a glass wool layer and provided with an aluminium laminated outer jacket.
The thermal insulation is suitable for preventing condensation and minimizing heat loss and loss of cold.
application
- insulation in air supply systems
- air conditioning systems
- thermal insulation in order to prevent heat or cold loss
- prevention / removal of condensation
|
Specifications |
|
|---|---|
| temperature range: | |
inner duct: |
-30 °C to 250 °C |
outer jacket: |
-30 °C to 140 °C |
| operating pressure: | max. +3000 Pa |
| operating air velocity: | max. 30 m/s |
| bending radius: | min. 0.54 x ∅ + 25 mm |
| diameter range: | 82 - 406 mm |
| standard length: | 10 mtr |
|
Construction |
|
|---|---|
| inner duct: | aluminium/polyester laminate |
| glass wool blanket: | 25 mm, 16 kg/m³ |
r-value: |
0.65m² K/W (ASTM C177-76) |
| outer jacket: | aluminium/polyester laminate |
| appearance: | aluminium |
|
Technical specifications |
|
|---|---|
Dutch specification |
|
German specification |
|
English specification |
|
French specification |
|
Graphs
|
|
|---|---|
|
pressure loss (download as .PDF or as .PNG) |
|
Product images
|
|
|---|---|
|
Certificates |
||
|---|---|---|
Europe |
EN 13501-1 | B-s1,d0 |
France |
NF | M1 |
NEN 13180 |
|---|
The Isodec CE fulfills all the requirements and are classified as specified within NEN 13180: "Ventilation for buildings – Ductwork - Dimensions and mechanical requirements for flexible ducts". |
| 82 | DIXCE082 | 1 | 98 |
| 102 | DIXCE102 | 1 | 72 |
| 127 | DIXCE127 | 1 | 66 |
| 152 | DIXCE152 | 1 | 50 |
| 160 | DIXCE160 | 1 | 45 |
| 180 | DIXCE180 | 1 | 32 |
| 203 | DIXCE203 | 1 | 32 |
| 229 | DIXCE229 | 1 | 24 |
| 254 | DIXCE254 | 1 | 21 |
| 305 | DIXCE305 | 1 | 15 |
| 315 | DIXCE315 | 1 | 15 |
| 356 | DIXCE356 | 1 | 8 |